2 
NT579-NT579 RS485  
TECSYSTEM SHANGHAI 
1) NT579 TECHNICAL 
INTRODUCTION 
 
NT579 is a microprocessor electronic device designed to integrate the ther-
mal control of resin-cast transformers . 
 
The monitoring unit has separated and independent inputs and outputs: 
 
3 3-wire Pt100 inputs for each winding (total 3 inputs) 
2 relays for Alarm - Trip signalling 
1 FAULT common relay (sensor fault, monitoring unit working anomaly) 
 
SUPPLY 
  
· Rated values: 18~36 Vdc  
COMMUNICATION  ON DIGITAL OR       
AD VERSION 
 
· RS485 MODBUS RTU 
INPUTS (Figure 2 Page 11) 
  
 3 3-wire PT100 sensor inputs. 
· Removable rear terminals 
 
  Input  channels  protected  against 
electromagnetic noises 
  
OUTPUTS (Figure 2 Page 11) 
  
 2 relays ALARM-TRIP with 6A-250Vac 
resistive contacts (cosΦ=1) 
 
·  1  FAN  output  at  250Vac  Max,  50/60 
Hz (max current 12A with cosΦ=1) 
 
·   1   alarm   relay   for   sensor   fault   or 
working anomaly  (FAULT)  with 6A-250Vac 
resistive contacts (cosΦ=1)