System Test Instructions
This section provides guidelines for testing the Tek-CARE300III system. As mentioned previously, we
recommend that the installer connect and test the system in sections, to allow for easier identification of
problem locations. Before testing a system, perform a complete walk through of the facility, and be cer-
tain to:
l verify that all components of the system to be tested are completely installed.
l verify that all patient stations that require them have call cords attached.
l verify that all pull cord or hand pull stations are in the reset position.
Using the System Operating Instructions on page 17 for reference, activate and observe the system oper-
ation for every component connected to the system. While initial testing must be performed in sections,
a complete system test must be performed once all components are connected to the system. This entails
activating every system component and verifying its operation a final time before considering the install-
ation complete.
We recommend that the system be periodically tested as indicated in this chapter to verify that the sys-
tem is in good operating condition. If problems are encountered, contact qualified service personnel for
system repair or maintenance. The next chapter, System Maintenance Instructions on page 26, indicates
which items may be serviced by on-site maintenance personnel.