Temperzone UC8 Troubleshooting Guide
Page 9 of 24
No
Yes
No
Yes
DRED energy restriction is active:
Wait until DRED energy restriction condition ends.
If DRED function is not required:
Air-to-air units: Inputs D1, D2, D3 should be open
circuit (Note: Inputs D1 and D2 may be used to
control Quiet and Dry modes.)
Hydronic units: Input D3 should be open circuit.
Chillers: Inputs D1, D2, D3 should be open circuit
Display shows a
flashing dot ●?
Display shows dr?
Display shows a
code listed in
chapters 11, 12
or 13?
The controller has detected a fault.
Refer to chapters 11, 12 and 13.
Yes
es
No
Contact Temperzone customer service.
Check wiring between UC8 and
the thermostat.
Continued from previous page.
Satellite dish shown
on t-stat display?
Yes
No
TZT-100 or SAT-3
wall thermostat?
No
Yes
Display shows
diFF-P?
Pressure differential is too high to allow the inverter
compressor to start:
Wait until the pressures have equalised.
Ensure valves are open.
Ensure the EEV operates correctly.
Yes
es
No
Correct
compressor
model selected?
Change the compressor model selection.
Yes
es