10
1.4 Technical Specifications
MODEL DS340H DS360H DS380H
Output (KVA) 40 kVA 60 kVA 80 kVA
Output (KW) 36 kW 54 kW 72 kW
Output Power Factor
INPUT
Number of Phases 3 Phase + Neutral
Input Voltage 220/380, 230/400 or 240/415 Vac
Input Voltage Tolerance +20% , -25% (+15% at 240/415Vac)
Input Power Factor (PF) 0,98 - 0,99 (at full load)
Input THDI <= 5% (at full load)
Input Frequency
50/60 Hz. ±10%
By-pass Voltage 220/380, 230/400 or 240/415 Vac 3 Phase + Neutral
By-pass Frequency
50 Hz. ±2%
RFI Level EN62040-2
OUTPUT
Number of Phases 3 Phase + Neutral
Output Voltage 220/380, 230/400 or 240/415 Vac
Output Voltage Tolerance
±1%
Output Frequency 50/60 Hz
Output Frequency Tolerance (Synchronous)
±2%
Output Frequency Tolerance (Battery)
±0,1% (free/battery operation mode)
Efficiency (100% Load) up to 94%
Load Crest Factor 3:1
Output Voltage THD (linear load) <=2%
Overload 125% Load 10min. , 150% Load 1min.
BATTERY
Total Number 60 blocks 12V (2x30 serial 60 batteries)
Float Charge Voltage (25
C)
± 405V DC
End of Discharge Voltage
± 300V DC
Battery Test Automatic and Manual
Boost Charge Available
COMMUNICATION INTERFACES
RS232 Com Port 2 each standard (COM1 and COM2)
External Temperature Measurement Input Available (standard)
RS485 Comm. Port Optional
Remote Monitoring Panel Optional
SNMP Adapter Optional
Modbus Adapter Optional
Alarm Relay Contacts 4 each dry contacts (function programmable) 8 optional
Digital Inputs 2 each optional
Emergency Power-Off Input Available (standard)
ENVIRONMENT
Operating Temperature 0 – 40
C
Operating Humidity <= %90 (non-condensing)
Acoustic Noise <62dB
Dimensions (WxDxH) (mm) 515 x 855 x 1450
Device Type and Protection Class Class 1 – IP20
Weight (Without Batteries) (app. kgs) 175 180 194