Programming
INS 034-9 31
Zone 1 will change (from Entry/Exit) into Guard and Zone 2 will change (from
Inhibited Entry) into Entry/Exit.
24 Hour zones (Fire, PA and Tamper), Keyswitch zones and Push to Set zones
should be monitored constantly and should NOT be programmed to change
when the system is part set.
3.10.1
Programming the Zones that will Change to Entry/Exit
#"
This suite defines the zones which will be changed into Entry/Exit zones on part
set. For example the
Veritas
is factory set with Zone 2 included. Thus the Zone
Type of Zone 2 will be changed (from Inhibited Entry) into Entry/Exit on part set.
Enter
#"
.
The zone lights of the zones which are currently included will
illuminate.
Press the appropriate numbered button(s) of the zone(s) to be
included or excluded. Press
,
.
The system will chime to confirm that the
new suite has been accepted. The system will then automatically revert to the
Programming Menu and all the zone lights will illuminate.
3.10.2
Programming the Zones that will Change to Inhibited Entry
##
This suite defines the zones which will be changed into Inhibited Entry zones on
part set. For example the
Veritas
is factory set with no zones included. Thus no
zones will be changed into Inhibited Entry.
Enter
##
.
The zone lights of the zones which are currently included will
illuminate.
Press the appropriate numbered button(s) of the zone(s) to be
included or excluded. Press
,
.
The system will chime to confirm that the
new suite has been accepted. The system will then automatically revert to the
Programming Menu and all the zone lights will illuminate.
3.10.3
Programming the Zones that will Change to Guard
#$
This suite defines the zones which will be changed into Guard zones on part set.
For example the
Veritas
is factory set with Zone 1 included. Thus the Zone Type of
Zone 1 will be changed (from Entry/Exit) into Guard on part set.
Enter
#$
.
The zone lights of the zones which are currently included will
illuminate.
Press the appropriate numbered button(s) of the zone(s) to be
included or excluded. Press
,
.
The system will chime to confirm that the
new suite has been accepted. The system will then automatically revert to the
Programming Menu and all the zone lights will illuminate.
3.11
Programming the Date and Time
1)
It is
ESSENTIAL
to program the current date (
#&
) and time (
#'
) for
correct operation of the service timer(s).
2)
Programming the service timers (
#)
,
#*
,
#(
) is prevented unless the
current date (
#&
) has first been programmed.
3)
If the panel is completely powered down it will attempt to store the current
time and date in NVM and continue from this point when it is powered up.