TS 970 Transfer Switch
PM163 REV 0 20/02/05 32 Thomson Power Systems
11. SHORT CIRCUIT WITHSTAND AND CLOSING RATINGS (ANY
BREAKER)
BASIC MODEL
RATED
CURRENT
(AMPS)
MAX
VOLTAGE
(VAC)
WITHSTAND
CURRENT RATING
(50m SEC) ANY
BREAKER
(AMPS RMS SYS)
WITHSTAND
CURRENT RATING
(17m SEC) ANY
BREAKER
(AMPS RMS SYS)
TS 97xA-0100
480V
100A
5,000
5,000
TS 97xA-0150
480V
150A
14,000
14,000
TS 97xA-0200
480V
200A
14,000
14,000
TS 97xA-0250
480V
250A
14,000
14,000
TS 97xA-0400
480V
400A
14,000
14,000
TS 97xA-0600
480V
600A
35,000
85,000
TS 97xA-0800
480V
800A
42,000
100,000
TS 97xA-1000
480V
1000A
42,000
100,000
TS 97xA-1200
480V
1200A
50,000
100,000
1. For other model types not shown, contact Thomson Power Systems for further information.
Note : Refer PM167 supplement document for short-circuit withstand / closing and short
time ratings specific circuit breaker manufacturer and type listing.