PRON NA60-MB0
Version 3.50
PRON NA60-MB0 Remote Setting Manual
Page: 21 of 59
VAR REF IDX DIM TYPE Range Um Kv ENUM
READINGS
Diagnostic
MINOR Fail alarm 1x 3 1 BIT 0=NO, 1=YES
Protection and controls 1x 4 1 BIT 0=OUT OF SERVICE, 1=ON
SERVICE
System diagnostic 3x 81 1 WORD 0="OK",1="FATAL",2="MAJO
R",3="MINOR"
Device diagnostic 1x 5 1 BIT 0=OK, 1=NOT OK
Program diagnostic 3x 82 1 WORD 0="OK",1="NOT
OK",2="Disappeared"
Data-base boot 3x 83 1 WORD 0="OK",1="NOT
OK",2="Disappeared"
Data-base run-time 3x 84 1 WORD 0="OK",1="NOT
OK",2="Disappeared"
DSP boot 3x 85 1 WORD 0="OK",1="NOT
OK",2="Disappeared"
DSP run-time 3x 86 1 WORD 0="OK",1="NOT
OK",2="Disappeared"
Memory boot 3x 87 1 WORD 0="OK",1="NOT
OK",2="Disappeared"
Memory run-time 3x 88 1 WORD 0="OK",1="NOT
OK",2="Disappeared"
Serial flash startup 3x 89 3 STR
Serial flash run-time 3x 92 3 STR
Data Bus heavy 3x 95 1 WORD 0="OK",1="NOT
OK",2="Disappeared"
Data Bus minor 3x 96 1 WORD 0="OK",1="NOT
OK",2="Disappeared"
Protection I/O assigned verify startup 3x 97 1 WORD 0="OK",1="NOT
OK",2="Disappeared"
Protection I/O assigned verify run-time major 3x 98 1 WORD 0="OK",1="NOT
OK",2="Disappeared"
Protection I/O assigned verify run-time minor 3x 99 1 WORD 0="OK",1="NOT
OK",2="Disappeared"