FUNCTION CHARACTERISTICS
75
NG10 - Manual - 04 - 2022
inside Read \ Selective block - BLOCK2 \ Block2 input menu) and can drive an output relay and
or a LED (tB-Kand or tB-Kparameters inside Set \ Profile A(or B) \ Selective block - BLOCK2 \
Selective block IN submenu)
With a setting other than 0.00 s, the t
B-Iph
and t
B-IE
timers may be used to have a backup protection
available against pilot wire short circuit.
[1]
The t
B-Iph
and/or t
B-IE
timers must be adjusted according the following rule (example for t
B-Iph
):
t
B-Iph
= t
F
v
+ e
t
+ e
s
where t
F
v
is the value of block output timer related to the downstream relay (example t
F-Iph
), e
t
is a
chronometric selectivity margin to apply in comparison to the t
B-Iph
time related to the downstream
relay (does not take into account if such margin has been considered for the t
F-Iph
setting), e
s
is a
safety margin. The chronometric selectivity applied among the t
B-x
times of the relays in accelerated
logic system allows to avoid more the contemporary circuit breaker opening after the clearing of a
fault in a line of concomitant plant to the short-circuit of the pilot wires concerning the same line.
Note 1 In the absence of suitable provisions, a short circuit on a pilot wire causes the block of the receiving relay, so a possible fault (contemporary or
following) inside the protected zone, cannot be cleared that being the case the protective relay blocked.
Binary input INx
T 0
Logic
INx
t
ON
INx
t
ON
INx
t
OFF
T0
n.o.
n.c.
INx
t
OFF
Binary input INx
T 0
Logic
INx
t
ON
INx
t
ON
INx
t
OFF
T0
n.o.
n.c.
INx
t
OFF
Binary input INx
T 0
Logic
INx
t
ON
INx
t
ON
INx
t
OFF
T0
n.o.
n.c.
INx
t
OFF
Block2 IPh
Block2 IPh/IE
ModeBLIN1
PulseBLIN1
T 0
Pilot wire
Diagnostic
Pulse BLIN1
Block2-in-diagram.ai
1
1
1
1
BLK2IN xx
&
&
&
Pilot wire input
No pulses
Permanently “ON”
xxBLK2IN
BLK2IN-Iph
Start xx
Trip xx
BLK2IN I>
&
&
Block2 input enable (I> element)
Block2 input enable (I>, I>>, I>>>, IE>, IE>>, IE>>>, elements)
(ON Enable)
&
I>BLK2IN
Start I>
Trip I>
Iph Block2
IE Block2
BLK2IN-IE
tB timeout
FROM EARTH FAULT PROTECTIONS
FROM ANY PROTECTIONS
FROM PHASE PROTECTIONS
OFF
ON IPh
ON IPh/IE
ON IE
BLIN1
Block2 IE
Breaked BLIN1
TRIPPING MATRIX
(LED+RELAYS)
1
1
Shorted BLIN1
Schema funzionale relativo ai segnali d’ingresso del blocco selettivo (Block2)
T0
t
B-Iph
t
B-Iph
t
B-IE
T0
t
B-IE