Creation: 01.31 - 2014 2-4-9
Generator and Controls (cont.)
4. Poor regulation, or erratic
voltage output
A. The engine is not a rated
speed, or the engine speed is not
stable.
A. Ensure that the J1939 bus
connections are in good condition.
Consult chapter 5 for engine
performance troubleshooting.
Contact the engine manufacturer
B. Circuit components inside the
GCM are defective.
C. The engine is overloaded.
C. Reduce the load at the aircraft
to the rating of the TLD generator.
Overloading can also occur for a
short period when the aircraft first
D. The engine is not producing full
power.
troubleshoot engine performance
issues. Contact the engine
manufacturer or TLD if necessary.
E. The engine charging voltage is
less than 24VDC.
troubleshoot engine charging
system issues. Contact the engine
manufacturer or TLD if necessary.
F. Fault in the generator exciter
F. Refer to the generator manual.
The exciter may require
5. Voltage recovery is slow (takes
more than 3 seconds) when the
A. Faulty engine computer or
other performance issue.
troubleshoot engine performance
B. Check the fuel supply lines and
fuel filter. Repair or replace if it is
C. Circuit components inside the
GCM are defective.