12
ENGLISH
ENGLISH
3. Set the type of regeneration:
Press the button DOWN to set the type of regeneration:
· A-01 = Delayed downflow volumetric regeneration
· A-02 = Regeneration instant volumetric downflow
· A-03 = Delayed regeneration downflow volumetric intelligent (not to use)
· A-04 = Instant regeneration downflow intelligent volumetric (not use)
To change it press the UP key, and confirm with the "menu / confirmation" key:
A-01 = delayed regeneration (regeneration will always be done at a preset time, once the volume of
water is exhausted).
A-02 = instantaneous regeneration (regeneration will be done upon reaching the predetermined water
volume, regardless of the time of day).
A-03 = intelligent delayed regeneration (regeneration will always be done at a preset time, once the
volume of water is exhausted), calculating the volume of water from the inlet hardness in mmol / Lt.
(Result of dividing ºF / 10).
A-04 = intelligent instant regeneration (the regeneration will always be done to the depletion of the
resin, once the volume of water is consumed), calculating the volume of water from the inlet hardness
in mmol / Lt. (Result of dividing ºF / 10).
Button “UP”
Button “DOWN”
Button “MENU”
Button “MENU”
4. Configuration of units of measurement:
Let's define the units of measure of the valve. To do this, press the button "DOWN" and we will see the units
of measurement:
· HU-01 = m
3
(we recommend using this parameter)
· HU-02 = Gallons
· HU-03 = Liters
A-01 A-02 A-03 A-04