D4 1600XPi Series UPS Installation and Operation Manual – 60616-014
10kVA – H3BG2L100C61T
(Runtimes are approximate)
UPS ESTIMATED RUNTIME WITH ONLY INTERNAL BATTERIES @ .85pf
Rating PF Output Volt-
age
Rated I Rated Load
%
Output
Watts
# Batt # Strings Nominal Runtime
10 0.85 240 41.67 0.10 850 24 1 288 72
10 0.85 240 41.67 0.20 1700 24 1 288 42
10 0.85 240 41.67 0.30 2550 24 1 288 25
10 0.85 240 41.67 0.40 3400 24 1 288 17
10 0.85 240 41.67 0.50 4250 24 1 288 12
10 0.85 240 41.67 0.60 5100 24 1 288 10
10 0.85 240 41.67 0.70 5950 24 1 288 9
10 0.85 240 41.67 0.80 6800 24 1 288 7
10 0.85 240 41.67 0.90 7650 24 1 288 5
10 0.85 240 41.67 1.00 8500 24 1 288 5
UPS ESTIMATED RUNTIME WITH INTERNAL BATTERIES AND 1 MATCHING BATTERY CABINET @ .85pf
Rating PF Output Volt-
age
Rated I Rated Load
%
Output
Watts
# Batt # Strings Nominal Runtime
10 0.85 240 41.67 0.10 850 24 4 288 300
10 0.85 240 41.67 0.20 1700 24 4 288 150
10 0.85 240 41.67 0.30 2550 24 4 288 105
10 0.85 240 41.67 0.40 3400 24 4 288 82
10 0.85 240 41.67 0.50 4250 24 4 288 70
10 0.85 240 41.67 0.60 5100 24 4 288 57
10 0.85 240 41.67 0.70 5950 24 4 288 50
10 0.85 240 41.67 0.80 6800 24 4 288 44
10 0.85 240 41.67 0.90 7650 24 4 288 40
10 0.85 240 41.67 1.00 8500 24 4 288 35
UPS ESTIMATED RUNTIME WITH INTERNAL BATTERIES AND 2 MATCHING BATTERY CABINETS @ .85pf
Rating PF Output Volt-
age
Rated I Rated Load
%
Output
Watts
# Batt # Strings Nominal Runtime
10 0.85 240 41.67 0.10 850 24 7 288 300
10 0.85 240 41.67 0.20 1700 24 7 288 300
10 0.85 240 41.67 0.30 2550 24 7 288 180
10 0.85 240 41.67 0.40 3400 24 7 288 135
10 0.85 240 41.67 0.50 4250 24 7 288 112
10 0.85 240 41.67 0.60 5100 24 7 288 98
10 0.85 240 41.67 0.70 5950 24 7 288 86
10 0.85 240 41.67 0.80 6800 24 7 288 72
10 0.85 240 41.67 0.90 7650 24 7 288 65
10 0.85 240 41.67 1.00 8500 24 7 288 60