D71600XPi Series UPS Installation and Operation Manual – 60616-014
22kVA – H3BG2L220C61T
(Runtimes are approximate)
UPS ESTIMATED RUNTIME WITH ONLY INTERNAL BATTERIES @ .85pf
Rating PF Output Volt-
age
Rated I Rated Load
%
Output
Watts
# Batt # Strings Nominal Runtime
22 0.85 240 91.67 0.10 1870 24 2 288 78
22 0.85 240 91.67 0.20 3740 24 2 288 40
22 0.85 240 91.67 0.30 5610 24 2 288 23
22 0.85 240 91.67 0.40 7480 24 2 288 16
22 0.85 240 91.67 0.50 9350 24 2 288 11
22 0.85 240 91.67 0.60 11220 24 2 288 9
22 0.85 240 91.67 0.70 13090 24 2 288 7
22 0.85 240 91.67 0.80 14960 24 2 288 6
22 0.85 240 91.67 0.90 16830 24 2 288 4
22 0.85 240 91.67 1.00 18700 24 2 288 3
UPS ESTIMATED RUNTIME WITH INTERNAL BATTERIES AND 1 MATCHING BATTERY CABINET @ .85pf
Rating PF Output Volt-
age
Rated I Rated Load
%
Output
Watts
# Batt # Strings Nominal Runtime
22 0.85 240 91.67 0.10 1870 24 5 288 165
22 0.85 240 91.67 0.20 3740 24 5 288 98
22 0.85 240 91.67 0.30 5610 24 5 288 65
22 0.85 240 91.67 0.40 7480 24 5 288 51
22 0.85 240 91.67 0.50 9350 24 5 288 42
22 0.85 240 91.67 0.60 11220 24 5 288 32
22 0.85 240 91.67 0.70 13090 24 5 288 26
22 0.85 240 91.67 0.80 14960 24 5 288 21
22 0.85 240 91.67 0.90 16830 24 5 288 18
22 0.85 240 91.67 1.00 18700 24 5 288 16
UPS ESTIMATED RUNTIME WITH INTERNAL BATTERIES AND 2 BATTERY MATCHING CABINETS @ .85pf
Rating PF Output Volt-
age
Rated I Rated Load
%
Output
Watts
# Batt # Strings Nominal Runtime
22 0.85 240 91.67 0.10 1870 24 8 288 300
22 0.85 240 91.67 0.20 3740 24 8 288 150
22 0.85 240 91.67 0.30 5610 24 8 288 105
22 0.85 240 91.67 0.40 7480 24 8 288 82
22 0.85 240 91.67 0.50 9350 24 8 288 63
22 0.85 240 91.67 0.60 11220 24 8 288 53
22 0.85 240 91.67 0.70 13090 24 8 288 46
22 0.85 240 91.67 0.80 14960 24 8 288 42
22 0.85 240 91.67 0.90 16830 24 8 288 36
22 0.85 240 91.67 1.00 18700 24 8 288 30