231600XPi Series UPS Installation and Operation Manual – 60616-014
TABLE 10.1: INITIAL BATTERY PARAMETER SETTINGS - MATCHING BATTERY CABINETS
Parameter Description UPS
Size
UPS
Only
UPS +
1 BC
1
UPS +
2 BC
1
511 Internal Battery Capacity in A-hr All 9 9 9
512 # Internal Batteries in Series String 3.6 kVA 12 12 12
5.2–6 kVA 18 18 18
8–22 kVA 24 24 24
513 # Internal Battery Strings in Parallel 3.6–10 kVA 1 1 1
14–22 kVA 2 2 2
522 Enable Ext. Battery Cabinet BC1 3.6–22 kVA Disable Enable Enable
523 Enable Ext. Battery Cabinet BC2 3.6–22 kVA Disable Disable Enable
524 External Batt. Cabinet Status All 0 1 1
525 # External Batt. Packs in Series String
(H3B-BC-0370)
3.6 kVA 0 12 12
(H3B-BC-0650) 6 kVA 0 18 18
(H3B-BC-1825) 8–22 kVA 0 24 24
526 # External Batt. Strings in Parallel
(H3B-BC-0370)
3.6 kVA 0 3 6
(H3B-BC-0650) 5.2–6 kVA 0 2 4
(H3B-BC-1825) 8–22 kVA 0 3 6
527 External Battery Capacity in A-hr All 0 9 9
1 These settings apply to 1600XPi matching battery cabinets.
TABLE 10.2: INITIAL BATTERY PARAMETER SETTINGS - NON-MATCHING BATTERY CABINETS
Parameter Description UPS
Size
UPS +
1 BC
1
511 Internal Battery Capacity in A-hr All 9
512 # Internal Batt. Packs in Series String 3.6 kVA 0
5.2–6 kVA 0
8–22 kVA 0
513 # Internal Batt. Strings in Parallel 3.6–22 kVA 1
522 Enable Ext. Battery Cabinet BC1 All Disable
523 Enable Ext. Battery Cabinet BC2 All Disable
524 External Batt. Cabinet Status All 1
525 # External Batteries in Series String 3.6 kVA 12
5.2–6 kVA 18
8–22 kVA 24
526 # External Batt. Strings in Parallel 3.6–22 kVA See Note 3
527 External Battery Capacity in A-hr All 9
1 Battery runtimes on the UPS display will not be accurate when using a non-Toshiba external battery cabinet.
2. Internal battery trays MUST be removed before connecting UPS to non-matching battery cabinet.
3. Set parameter 526 as (External Battery Capacity – 9 Amp Hr) / 9 Amp Hr.