10Zone setting
What is zone?
A zone is a control unit consisting of a combination of any indoor units and the settings of indoor units in a zone
can be configured collectively.
You can make up to 64 zones pairing any of up to 64 groups in a line. By using lines 1 and 2, you can set up to
128 zones in total.
As factory default, each zone contains one group to make zone numbers equal to group numbers.
Setting zones
Register groups in a zone or cancel them.
(1) Change the mode to the zone setting mode.
Press the button, button, and ZONE button simultaneously for at least 4 seconds.
(The displayed zone number flashes and the Smart Manager with data analyzer enters the zone setting
mode. Indicates CODE No. “E1”.)
(2) Select the zone to be set.
Select the zone number to be set with the ZONE or button, and then press the button to fix the
selection.
(When the selection has been fixed, the selected zone number lights.)
When selection of zone has been fixed, the marks of the group numbers registered in the zone light up.
(3) Change registration of groups in a zone.
Register groups in a zone.
1. Select the group number to be set with the GROUP or button. Pressing the SET TEMP. or
button skips the group number by +16 or by -16.
2. Press the button.
The registered group number stops flashing and lights still.
3. Pressing the button restores the state before the button is pressed.
4. To continue registration of groups, repeat this procedure from the 1.
NOTE
No zone data has been stored at this time. If the ZONE or button is pressed before the registration
change is fixed, the set content for registration change is discarded.
(4) Fix the registration change.
Press the button. The set content for registration change is stored in the memory.
* After the memory write operation has been completed, the Smart Manager with data analyzer exits the zone
setting mode.
NOTE
Any indoor unit cannot be registered on to two or more zones at the same time.
If you register a group of a zone on to another zone, the group is eliminated from the old zone.
Zone registration of a group cannot be cancelled. To exclude a registered group from a zone, register it on
another zone.