131600XPi Series UPS Installation and Operation Manual – 60616-014
Input and Jumper wire/bus strip connection for:
208 Vin – Using provided jumper, connect terminals 11 – 12.
REMOTE1
208
EPO2EPO1
REMOTE2
COM
240GX3
1
L2 G X1 X2 N
2 3
12 1413 15
8765 114
16 17
L1
Factory Installed N - G Jumper
Jumper
208 Vin
Rmt Contacts
EPO
NONO
120 V
240 V
120 V
208 V
32 V 88 V
240 Vin – Using provided jumper, connect terminals 13 – 12.
REMOTE1
208
EPO2EPO1
REMOTE2
COM
240GX3
1
L2 G X1 X2 N
2 3
12 1413 15
8765 114
16 17
L1
Factory Installed N - G Jumper
Jumper
240 Vin
Rmt Contacts
EPO
NONO
120 V
240 V
120 V
208 V
32 V 88 V
Output Cabling for:
120 Vout
Connect load across Terminals 4 – 6 or 6 – 7.
208 Vout
Connect load across terminals 5 – 7.
240 Vout
Connect load across terminals 4 – 7.
120 V
120 V
GX3G X1 X2 N
3 87654
Factory Installed N - G Jumper
208 Vout
GX3G X1
X2
N
3 87654
Factory Installed N - G Jumper
240 Vout
GX3G X1 X2 N
3 87654
Factory Installed N - G Jumper