351600XPi Series UPS Installation and Operation Manual – 60616-014
15.1 Battery Mimic Display (BAT)
Press BAT on the Mimic Display to view the parameters for the internal and external batteries. Internal battery congura-
tions are either 1 or two strings of battery packs in parallel, depending on the UPS capacity. External battery cabinets are
all wired with three strings of battery packs in parallel.
INTERNAL BATTERY
Press INTERNAL BATTERY to view the parameter values for the internal battery set.
Press Internal Battery to view Internal Battery parameters.
EXTERNAL BATTERY CABINETS (MATCHING)
The new Smart Charger on the 1600XPi connects via a RS-232 cable that ships with the Matching External Battery
Cabinets. Set the external battery cabinet parameters as shown in Section 11.2. Now the UPS can monitor the external
battery cabinet(s)
• UPS can monitor external charger voltage and current
• UPS can detect battery disconnect fault in backup mode with load
• UPS display shows which battery string is disconnected(See Section 16.2)
• Battery cabinet detect over-voltage fault
• Battery cabinet detects charger over-current faults
Press the EXTERNAL BATTERY to view the Battery Cabinet summary screen. (View results for one cabinet at a time.)
Press MONITOR to view the parameter details for that External Battery Cabinet.
On-Line
DVCOH
EXTBC1
Main Monitor Settings Records
12:35 PM
INV
HOME
USR
96% 100%
Internal Battery
External Battery 1
External Battery 2
On-Line
DVCOH
EXTBC1
Main Monitor Settings Records
12:35 PM
INV
HOME
USR
BAT 1/1
501 Battery Voltage
503 Discharge Current
506 Charger Status
508 Cal Battery Vsd
547 Cal LB Level
200 Vdc
0.0 Adc
Normal
172 Vdc
194 Vdc
96% 100%
On-Line
DVCOH
EXTBC1
Main Monitor Settings Records
12:35 PM
INV
HOME
USR
BAT 1/1
576 BC1 Vin
578 BC1 Chg Current
582 BC1 Status
583 BC1 Chg Voltage
585 BC1 AmbientTemp
400 Vdc
1.0 Adc
0X0400
327 Vdc
29 C
96% 100%
On-Line
DVCOH
EXTBC1
Main Monitor Settings Records
12:35 PM
INV
HOME
USR
96% 100%
Internal Battery
External Battery 1
External Battery 2
On-Line
DVCOH
EXTBC1
Main Monitor Settings Records
12:35 PM
INV
HOME
USR
96% 100%
Monitor
Battery Cabinet 1
Voltage DC: 280 V
Charge %: 90 %
Current: 1.00 A