143
2. DN Setting
• Hydro unit DN code setting is available only for the header remote controller.
• Set DN codes for various operation modes with the remote controller.
2-1. How to set hydro unit DN
<Procedure> Perform the following when no operation is in progress.
1 Press the [ ] button and the [ ] button at same time for 4
seconds or longer on the top screen to display the “FIELD SETTING
MENU”.
2 Press the [ ] / [ ] button to select “Hydro Unit DN” on the
FIELD SETTING MENU screen, then press the [ ] button.
3 Press the [ ] / [ ] button to select DN or Data, then press the
[ ] / [ ] button to set the value.
4 Press the [ ] button. The set value is registered.
FIELD SETTING MENU(2/2)
Service monitor
Hydro Unit DN
SET
Remote controller DN
Reset power consumption data
Sensor information
0010
Hydro Unit DN
(DN) Data
FIX
0070
e
d
oC