– 13 –
(50Hz)
Model name
MMD-AP
∗∗∗∗
BHP1-E(TR)
Cooling/Heating capacity
(Note 1) (kW)
Electrical
characteristics
Power supply
Running current (A)
Power consumption (kW)
Starting current (A)
Appearance
Dimension Height (mm)
Width (mm)
Depth (mm)
Total weight (kg)
Heat exchanger
Soundproof / Heat-insulating meterial
Fan unit
Controller
Connecting
pipe
Gas side (mm)
Liquid side (mm)
Drain port (mm)
Sound pressure level (Note 2)
(dB(A))
(High/Med./Low)
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by
JIS B 8615 based on the reference piping.
The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 m
height.
Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B 8616.
Normally, the values measured in the actual operating environment become larger than the indicated
valves due to the effects of external sound.
Note : Rated conditions Cooling: Indoor air temperature 27˚C DB/19˚C WB, Outdoor air temperature 35˚C DB
Heating: Indoor air temperature 20˚C DB, Outdoor air temperature 7˚C DB/6˚C WB
30-40-50-65-80-100-120 (7steps)
150
30 40 50
250
Remote controller
9.56.4
25(Polyvinyl chloride tube)
Air filter
Standard filter (Long life filter)
1phase 50Hz 230V(220V-240V)
Polyethlene foam
Centrifugal fan
9.5 12.7 15.9
Zinc hot dipping steel plate
Finned tube
275
700 1000 1400
750
0.26 0.29 0.42 0.52
0.61 1.07 1.23
0.038 0.043 0.062 0.077
0.094 0.172 0.198
0.45 0.50 0.73 0.90
1.06 1.85 2.13
Fan
Standard air flow (m³/h)
(Med./Low)
540
(450/360)
570
(480/390)
Motor output (W)
(Pa)
(factory setting)
External static pressure (Pa)
External static pressure
2.2/2.5 2.8/3.2 3.6/4.0 4.5/5.0 5.6/6.3 7.1/8.0 8.0/9.0 9.0/10.0 11.2/12.5 14.0/16.0 16.0/18.0
0076 0096 0126 0156 0186 0246 0276 0306 0366 0486 0566
23 30 40
800
(660/540)
1,200
(990/870)
1,260
(1110/930)
1,920
(1620/1380)
2,100
(1740/1500)
29/26/23
30/26/23 33/29/25 36/31/27 40/36/33
1. SPECIFICATIONS