– 15 –
29-EN 30-EN
Example:
072 type (MMY-MAP0726FT6P-UL)
036 type
Single port type FS unit
Single port type FS unit
024 type 012 type
Pipe Liquid pipe size Actual Piping length
L1 Ø1/2" 30 ft
L2 Ø3/8" 15 ft
L3 Ø3/8" 10 ft
L4 Ø3/8" 10 ft
L5 Ø3/8" 5 ft
L6 Ø3/8" 10 ft
L7 Ø1/4" 10 ft
Additional refrigerant charge amount(lbs) = [1] + [2]
= 4.4 lbs + 5.395 lbs
= 9.795 lbs
[1]. Compensation by capacity of outdoor unit (Table1)
= Compensation by 072 type
= 4.4 lbs
[2]. (Actual length of liquid pipe × Additional refrigerant charge amount per liquid pipe 1 ft (Table2)) × 1.3
= ((L7) × 0.017 lbs/ft + (L2+L3+L4+L5+L6) × 0.037 lbs/ft+(L1) × 0.071 lbs/ft) × 1.3
= ((10 ft) × 0.017 lbs/ft + (50 ft) × 0.037 lbs/ft+(30 ft) × 0.071 lbs/ft) × 1.3
= (0.17 lbs + 1.85 lbs + 2.13 lbs) × 1.3
= (4.15 lbs ) × 1.3
= 5.395 lbs
Lx : Actual total length of liquid pipe Ø1/4" (ft)
Ly : Actual total length of liquid pipe Ø3/8" (ft)
Lz : Actual total length of liquid pipe Ø1/2" (ft)
■ Calculation of additional refrigerant charge amount
Additional refrigerant charge amount (lbs) = [1] + [2]
[1]. Compensation by capacity of outdoor unit (Table1)
[2]. (Actual length of liquid pipe × Additional refrigerant charge amount per liquid pipe 1 ft (Table2)) × 1.3
NOTE
If the additional refrigerant amount indicates minus as the result of calculation, use the air conditioner without
additional refrigerant.
(Table1) Compensation by capacity of outdoor unit
Outdoor unit
capacity type
Model name
(Standard Model)
Compensation by
capacity type outdoor unit
(lbs)
072 type MMY-MAP0726FT6P-UL 4.4
096 type MMY-MAP0966FT6P-UL 6.6
120 type MMY-MAP1206FT6P-UL 17.6
144 type MMY-MAP1446FT6P-UL 24.3
168 type MMY-MAP1686FT6P-UL 30.9
192 type MMY-AP1926FT6P-UL 8.8
216 type MMY-AP2166FT6P-UL 13.2
240 type MMY-AP2406FT6P-UL 22.1
264 type MMY-AP2646FT6P-UL 26.5
288 type MMY-AP2886FT6P-UL 30.9
312 type MMY-AP3126FT6P-UL 33.1
336 type MMY-AP3366FT6P-UL 13.2
360 type MMY-AP3606FT6P-UL 24.3
384 type MMY-AP3846FT6P-UL 28.7
408 type MMY-AP4086FT6P-UL 30.9
432 type MMY-AP4326FT6P-UL 33.1
456 type MMY-AP4566FT6P-UL 37.5
Outdoor unit
capacity type
Model name
(Space Saving Model)
Compensation by
capacity type outdoor unit
(lbs)
192 type MMY-AP192S6FT6P-UL 8.8
240 type MMY-AP240S6FT6P-UL 22.1
288 type MMY-AP288S6FT6P-UL 30.9
336 type MMY-AP336S6FT6P-UL 37.5
(Table2) Actual length of liquid pipe × Additional refrigerant charge amount per liquid pipe 1 ft
Liquid pipe outer diameter (in) Ø1/4" Ø3/8" Ø1/2" Ø5/8" Ø3/4" Ø7/8"
Additional refrigerant amount lbs/ft 0.017 0.037 0.071 0.108 0.168 0.235
1122001001-2_EN-FR.indb 151122001001-2_EN-FR.indb 15 2/18/17 11:44 AM2/18/17 11:44 AM