– 9 –
Table 1
Indoor unit
capacity rank
Capacity code
Equivalent to HP
Equivalent to
capacity
*005 0.6 1.7
005 0.8 2.2
007 0.8 2.2
009 1 2.8
012 1.25 3.6
015 1.7 4.5
018 2 5.6
024 2.5 7.1
027 3 8
030 3.2 9
036 4 11.2
048 5 14
056 6 16
072 8 22.4
096 10 28
*005 Indoor model: MMU-AP0056MH*, MMD-AP0056SPH*, MMK-AP0054MHP*
Table 2
Outdoor unit
model name*1
(Standard model)
Capacity code
Max. No. of
indoor units*2
Equivalent to HP
Equivalent to
capacity
MMY-MAP0806* 8 22.4 18
MMY-MAP1006* 10 28 22
MMY-MAP1206* 12 33.5 27
MMY-MAP1406* 14 40 31
MMY-MAP1606* 16 45 36
MMY-MAP1806* 18 50.4 40
MMY-MAP2006* 20 56 41
MMY-AP2216* 22 61.5 49
MMY-AP2416* 24 68 54
MMY-AP2616* 26 73.5 58
MMY-AP2816* 28 80 63
MMY-AP3016* 30 85 64
MMY-AP3216* 32 90.4 64
MMY-AP3416* 34 95.4 64
MMY-AP3616* 36 100.8 64
MMY-AP3816* 38 106.4 64
MMY-AP4016* 40 112 64
MMY-AP4216* 42 120 64
MMY-AP4416* 44 125 64
MMY-AP4616* 46 130.4 64
MMY-AP4816* 48 135.4 64
MMY-AP5016* 50 140.8 64
MMY-AP5216* 52 145.8 64
MMY-AP5416* 54 151.2 64
*1 For combination of the outdoor units, refer to “Combination of outdoor units”.
*2 Under centralized control maximum 54 unit.
Coupling size of brazed pipe
Connected section
External size Internal size
K
ØC
G
ØF
(Unit: mm)
Standard outer dia.
of connected
copper pipe
Connected section
Min. thickness
of coupling
External size Internal size
Min. depth of
insertion
Oval value
Standard outer dia.
(Allowable difference)
CFKG
6.35 6.35 (±0.03)
6.45
(
)
+0.04
í0.02
7 6 0.06 or less 0.50
9.52 9.52 (±0.03)
9.62
(
)
+0.04
í0.02
8 7 0.08 or less 0.60
12.70 12.70 (±0.03)
12.81
(
)
+0.04
í0.02
9 8 0.10 or less 0.70
15.88 15.88 (±0.03)
16.00
(
)
+0.04
í0.02
9 8 0.13 or less 0.80
19.05 19.05 (±0.03)
19.19
(
)
+0.03
í0.03
11 10 0.15 or less 0.80
22.22 22.22 (±0.03)
22.36
(
)
+0.03
í0.03
11 10 0.16 or less 0.82
28.58 28.58 (±0.04)
28.75
(
)
+0.06
í0.02
13 12 0.20 or less 1.00
34.92 34.90 (±0.04)
35.11
(
)
+0.04
í0.04
14 13 0.25 or less 1.20
38.10 38.10 (±0.05)
38.31
(
)
+0.08
í0.02
15 14 0.27 or less 1.26
41.28 41.28 (±0.05)
41.50
(
)
+0.08
í0.02
15 14 0.28 or less 1.35
Selection of pipe size
¡ Capacity code of indoor and outdoor units
Selection of pipe material
For the indoor unit, the capacity code is decided at each capacity rank. (Table 1)
The capacity codes of the outdoor units are decided at each capacity rank. The maximum number of
connectable indoor units and the total value of capacity codes of the indoor units are also decided. (Table 2)
NOTE
Compared with the capacity code of the outdoor unit, the total value of capacity codes of the connectable
indoor units differs based on the height difference between the indoor units.
When the height difference between the indoor units is 15 m or less: Up to 135% of the capacity code
(Equivalent to HP) of the outdoor unit.
When the height difference between the indoor units is over 15 m: Up to 105% of the capacity code.
17-EN 18-EN