EasyManua.ls Logo

Toshiba MMY-MAP0806FT8P-E - Test Run

Toshiba MMY-MAP0806FT8P-E
37 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
– 31 –
1, 5
3
2, 4
ON / OFF
TEMP.
TIME
SET CL
FILTER
RESET
TEST
TIMER SET
1
Push and hold the button for more than
4 seconds. TEST appears on the LCD
display and the unit enters the trial mode.
(TEST is indicated on the LCD display
during the test run.)
TEST
2
Push the button.
3
Push the button to switch the
running mode to COOL or HEAT.
NOTE
Do not run the unit in any mode other than COOL or
HEAT.
You cannot change the temperature setting during
the test run.
Errors are detected as usual.
TEST
4
Push the button to stop running
after finishing the trial run.
The indication on the LCD display returns
to the status of procedure 1.
5
Push the button to exit the trial mode.
(TEST disappears on the LCD display and
the status changes to normal stopped
mode.).
10 Test run
Before test run
Confirm that the valve of the refrigerate pipe of the
outdoor unit is OPEN.
Before turning on the power, confirm that the
resistance between the terminal block of power
supply and the earth is more than 1 Mȍ using a
500 V megohmmeter.
Do not run the unit if it is less than 1 Mȍ.
CAUTION
To protect the compressor, turn on the power at
least 12 hours before the test run.
Methods of test run
When executing a test run using
a remote controller
Operate the system normally to check the running
condition using the wired remote controller. Follow
the instructions in the supplied Owner’s Manual when
operating the unit.
If you use a wireless remote controller for operations,
follow the instructions in the Installation Manual
supplied with the indoor unit.
To execute a test run forcibly under the condition that
the thermostat automatically turns the unit off due to
the indoor temperature, follow the procedure below.
The forcible test run will automatically stop after
60 minutes to prevent continuous forcible running and
return to normal running.
CAUTION
Do not use forcible running except for a test run as it
overloads the unit.
6
When the setup finished, push button.
(The setup is determined.)
Pushing button deletes the display and
returns to normal stop status.
(For some time after
button has been pushed,
the operation of the remote controller cannot be
accepted.)
61-EN 62-EN