F-GAS label
This product contains Àuorinated greenhouse gases
Chemical Name of Gas R410A
Global Warming Potential (GWP) of Gas 2088 (ex.R410A ref.AR4)
CAUTION
1. Stick the enclosed refrigerant label adjacent to the service ports for charging or recovering location and where
possible adjacent to existing nameplates or product information label.
2. Clearly write the charged refrigerant quantity on the refrigerant label using indelible ink. Then, place the
included transparent protective sheet over the label to prevent the writing from rubbing off.
3. Prevent emission of the contained Àuorinated greenhouse gas. Ensure that the Àuorinated greenhouse gas is
never vented to the atmosphere during installation, service or disposal. When any leakage of the contained
Àuorinated greenhouse gas is detected, the leak shall be stopped and repaired as soon as possible.
4. Only quali¿ed service personnel are allowed to access and service this product.
5. Any handling of the Àuorinated greenhouse gas in this product, such as when moving the product or recharging
the gas, shall comply under (EU) Regulation No. 517/2014 on certain Àuorinated greenhouse gases and any
relevant local legislation.
6. Periodical inspections for refrigerant leaks may be required depending on European or local legislation.
7. Contact dealers, installers, etc., for any questions.
Full opening of the valve
Open the valves of the outdoor unit fully.
MAP080
MAP100
MAP120
MAP140
MAP160
MAP180
MAP200
Balance pipe
Packed valve
Using a 4 mm-hexagonal wrench, fully open the valve shaft.
Liquid side
Ø12.7 packed valve
Using a 4 mm-hexagonal wrench, fully open the
valve shaft.
Ø15.9 packed valve
Using a 5 mm-hexagonal wrench, fully open the
valve shaft.
Discharge gas
side
Ball valve
Using a Àathead screwdriver, turn it counterclockwise by 90° until it hits the stopper. (Full open)
(1)
(2)
Service port
Valve unit
Using Àathead screwdriver, turn
it counterclockwise by 90° until
it hits the stopper. (Full open)
Flare nut
Position of screwdriver slot
Fully closed Fully opened
Slot
* When opened fully, do not apply excessive
torque after the screwdriver hits the
stopper; otherwise a problem may be
caused on the valve. (5 N•m or less)
Suction gas side
Ball valve
Using a wrench, turn the valve shaft counterclockwise by 90° until it hits the stopper. (Full open)
Fully closed Fully opened