– 18 –
EN
ID
ID
Power wiring selection
īš‡ Select the power supply cabling of each outdoor unit from the following specifications:
Cable 5-core, in conformance with design H07 RN-F or 60245 IEC 66.
īš‡ To decide nominal cross sectional area of conductor, refer to following table of Maximum Overcurrent Protection
(Amps).
MCA:Minimum Circuit Amps
MOCP:Maximum Overcurrent Protection (Amps)
Model name
Power Supply
MCA
(A)
MOCP
(A)
Phase and frequency Nominal Voltage
MMY-MAP0806*
3 N ~ 50 Hz 380 - 400 - 415 V
21.5 25
MMY-MAP1006* 26.1 32
MMY-MAP1206* 31.0 40
MMY-MAP1406* 35.8 50
MMY-MAP1606* 40.6 50
MMY-MAP1806* 44.9 50
MMY-MAP2006* 49.3 63
MMY-AP2216*
3 N ~ 50 Hz 380 - 400 - 415 V
57.1 63
MMY-AP2416* 62.0 80
MMY-AP2616* 66.8 80
MMY-AP2816* 71.6 80
MMY-AP3016* 76.5 100
MMY-AP3216* 81.3 100
MMY-AP3416* 85.6 100
MMY-AP3616* 89.8 100
MMY-AP3816* 94.2 125
MMY-AP4016* 98.6 125
MMY-AP4216*
3 N ~ 50 Hz 380 - 400 - 415 V
107.4 125
MMY-AP4416* 112.3 125
MMY-AP4616* 116.5 160
MMY-AP4816* 122.0 160
MMY-AP5016* 126.2 160
MMY-AP5216* 130.5 160
MMY-AP5416* 134.7 160
L1L2L3 N
L1L2L3 N L1L2L
3
N
Circuit breaker
(Earth leakage breaker)
Main switch
(Fuse)
Specifications for communication wiring
Design of communication wiring
Summary of communication wiring
U1 U2
U3 U4
W3
W1
W2
BA2U1UBA2U1UBA2U1UBA2U1U
BABABA
*1
*2
*3
CN02
CN81
CN02
CN81
CN02
CN81
CN81
U1
U2
S
U3
U4
U5
U6
S
U1
U2
S
U3
U4
U5
U6
S
CN81 U1 U2 A B CN81 U1 U2 A B CN81 U1 U2 A B CN81 U1 U2 A B
BABABABA
AB AB AB AB
CN81
U1 U2 A B CN81 U1 U2 A B CN81 U1 U2 A B CN81 U1 U2 A B
BABABABA
BABABABA
Outdoor unit
Header outdoor
Outdoor unit
Follower outdoor
Central remote
device (option)
Indoor unit
Single port type
FS unit
Single port type
FS unit
Single port type
FS unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Remote controller Remote controller Remote controller
Remote controller Remote controller Remote controller Remote controller
Multi port type FS unit (4 port)
W1 Control wiring between indoor and outdoor units (Shield wire)
W2 Control wiring between indoor units (Shield wire)
W3 Control wiring between outdoor units (Shield wire)
*1 When perform a central control, connect a relay connector
between [U1, U2] and [U3, U4] terminals in the header unit.
(At shipment from factory : No connection)
*2 Connection of shield wire must be connected
(Connected to all connecting sections in each Indoor unit)
*3 Group control
tinu roodnItinu roodnItinu roodnItinu roodnI
Remote controller Remote controller Remote controller Remote controller
Single port type FS unit
(Long piping model)
Single port type FS unit
(Long piping model)
Single port type FS unit
(Long piping model)
Single port type FS unit
(Long piping model)
35-EN 36-EN

Related product manuals