– 21 –
Screw size and tightening torque
Screw size
Tightening torque
(N•m)
Power supply terminal M6 2.5 to 3.0
Earth screw M8 5.5 to 6.6
¡ Communication wire connection
Get the communication wire through the cutout on the side of the electrical control box and connect it to the
communication wire terminals, then ¿x it with the communication cable clamp.
U1
U3
U4
U2
U5
U6
S
S
TO
INDOOR UNIT
TO
OUTDOOR UNIT
TO
CENTRAL
CONTROLLER
SHIELD SHIELD
U5, U6: Communication wiring between outdoor units
U3, U4: Central control device
U1, U2:
Communication wiring between indoor/outdoor units
S: Shield wire earth
Screw size and tightening torque
Screw size
Tightening torque
(N•m)
Communication wire terminal M4 1.2 to 1.4
Regulation of harmonic currents
This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to Ssc
(*1) at the interface point between the user’s supply and the public system. It is the responsibility of the installer or user
of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is
connected only to a supply with a short-circuit power Ssc greater than or equal to Ssc (*1)
Furthermore, when similar equipment or other equipment which may cause harmonic current emissions are to be
connected to the same interface point with this equipment, to reduce the risk of possible problems which may be
caused from addition of those harmonic current emissions, it is recommended to make sure that the short-circuit power
Ssc at the interface point is greater than the sum of the minimum Ssc required by all the equipment which will be
connected to the interface point.
Ssc (*1) :
Model Ssc (kW)
MMY-MAP0806FT8P-E
MMY-MAP0806FT8JP-E
1355
MMY-MAP1006FT8P-E
MMY-MAP1006FT8JP-E
1654
MMY-MAP1206FT8P-E
MMY-MAP1206FT8JP-E
1874
MMY-MAP1406FT8P-E
MMY-MAP1406FT8JP-E
2030
MMY-MAP1606FT8P-E
MMY-MAP1606FT8JP-E
2391
MMY-MAP1806FT8P-E
MMY-MAP1806FT8JP-E
2669
MMY-MAP2006FT8P-E
MMY-MAP2006FT8JP-E
2938