– 29 –
[ Set up example ]
[ 0E ] : Group setting
0 : Individual (Factory default)
1 : Group
[ 14 ] : Group address
0 : Individual
1 : Header unit
2 : Follower unit
[ FE ] : Branching system address (1~64)
Should not be duplicate in one system
Factory default : 99
[ FD ] : Priority operation mode
0 : Heating prioritized (Factory default)
1 : Cooling prioritized (The cooling is
prioritized even if setting only one unit in
one branching)
< In case of connecting one indoor unit>
Single port type FS unit
Piping
Control wiring
between indoor unit
and FS unit
(Within 15 m)
Remote
controller
Indoor unit
Indoor unit
Piping
Multi port type FS unit (*1)
Remote
controller
[ 0E ] : It is not necessary to set up
[ 14 ] : It is not necessary to set up
[ FE ] : It is not necessary to set up
[ FD ] : It is not necessary to set up
[ 0E ] : It is not necessary to set up
[ 14 ] : It is not necessary to set up
[ FE ] : It is not necessary to set up
[ FD ] : It is not necessary to set up
<In case of connecting one group operation of
indoor units>
Single port type FS unit
Piping
Control wiring
between indoor unit
and FS unit
(Within 15 m)
Remote controller
Indoor unit
Indoor unit
Multi port type FS unit (*1)
Remote controller
[ 0E ] : 1 1 1
[ 14 ] : 1 2 2
[ FE ] : It is not necessary to set up
[ FD ] : It is not necessary to set up
[ 0E ] : 1 1 1
[ 14 ] : 1 2 2
[ FE ] : It is not necessary to set up
[ FD ] : It is not necessary to set up
Group control
Piping
Group control
<In case of connecting two group operations of
indoor units>
Single port type FS unit
Piping
Control wiring
between indoor unit
and FS unit
(Within 15 m)
Remote
controller
Indoor unit
Indoor unit
Multi port type FS unit (*1)
Remote
controller
[ 0E ] : 1 1 1 1
[ 14 ] : 1 2 1 2
[ FE ] : 1 1 1 1
[ FD ] : 0 0 0 0
[ 0E ] : 1 1 1 1
[ 14 ] : 1 2 1 2
[ FE ] : 1 1 1 1
[ FD ] : 0 0 0 0
Group control Group control
Piping
Group control Group control
How to set up CODE No. [ 14 ]
It is necessary to set up group address in case of the
group control.
0 : Individual
1 : Header unit
2 : Follower unit
How to set up CODE No. [ FE ]
In cases other than connecting with one indoor unit or
one group in one branching, it is necessary to set up.
As for both single port type and multi port type, set
up CODE No. “FE” in one branching within the range
of 1~64.
This CODE No. should not be duplicate in one
system.
How to set up CODE No. [ FD ]
In cases other than connecting with one indoor unit or
one group in one branching, it is necessary to set up.
0 : Heating prioritized (Factory default)
1 : Cooling prioritized
In case of FE/FD without setting
Single port type FS unit
Piping
Control wiring
between indoor unit
and FS unit
(Within 15 m)
Remote controller
Group control
Indoor unit
Indoor unit
Piping
Multi port type FS unit (*1)
Remote controller
Group control
In case of FE/FD with setting
Single port type FS unit
Single port type FS unit
Piping
Piping
Control wiring
between indoor unit
and FS unit
(Within 15 m)
Control wiring
between indoor unit
and FS unit
(Within 15 m)
Remote controller
Remote
controller
Group control
Group control
Group control
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Piping
Piping
Multi port type FS unit (*1)
Multi port type FS unit (*1)
Remote
controller
Remote
controller
Group control
Group control
Group control
57-EN 58-EN