192 Q9 ASD Installation and Operation Manual
Table 8. My Function — Input Function Target and Monitor Output Function Selections.
Input Setting/Communication
Number
Function Resolution
FM/AM/FP
Input Setting
Comm.
Number
Monitor
Display
Input Setting
Comm.
Number
2000 FD00 3000 FE00 Output Frequency 0.01 Hz
2002 FD02 3002 FE02 Frequency Reference 0.01 Hz
2003 FD03 3003 FE03 Output Current 0.01%
2004 FD04 3004 FE04 DC Bus Voltage 0.01%
2005 FD05 3005 FE05 Output Voltage 0.01%
2015 FD15 3015 FE15 Compensated Frequency 0.01 Hz
2016 FD16 3016 FE16 Speed Feedback (Realtime) (See Note 1) 0.01 Hz
2017 FD17 3017 FE17 Speed Feedback (1 Sec Filter) (See Note 1) 0.01 Hz
2018 FD18 3018 FE18 Torque (See Note 2) 0.01%
2019 FD19 3019 FE19 Torque Command (See Note 2) 0.01%
2020 FD20 3020 FE20 Torque Current (See Note 2) 0.01%
2021 FD21 3021 FE21 Excitation Current 0.01%
2022 FD22 3022 FE22 PID Feedback Value 0.01 Hz
2023 FD23 3023 FE23 Motor Overload Ratio 0.01%
2024 FD24 3024 FE24 ASD Overload Ratio 0.01%
2025 FD25 3025 FE25 DBR Overload Ratio (Not Used) 1%
2028 FD28 3028 FE28 DBR Load Ratio (Not Used) 1%
2029 FD29 3029 FE29 Input Power 0.01 kW
2030 FD30 3030 FE30 Output Power 0.01 kW
2050 FD50 Light-Load High-Speed Load Torque Monitor 1 0.01%
2051 FD51 Light-Load High-Speed Load Torque Monitor 2 0.01%
3035 FE35 RR Input 1%
3036 FE36 V/I Input 1%
3037 FE37 RX Input (See Note 2) 1%
3038 FE38 RX2 (AI1) Input (See Note 2) 1%
3039 FE39 RX2 (AI2) Input 1%
3040 FE40 FM Output 1
3041 FE41 AM Output 1
Note 1: If no PG feedback is used an estimated speed value is displayed.
Note 2: My Function cannot process negative values — A negative value is processed by My Function as an absolute
value.