Q9 ASD Installation and Operation Manual 27
Figure 21. The Q9 ASD Electronic Operator Interface Features.
EOI Features
LCD Screen — Displays configuration information, performance data (e.g., output frequency, bus
voltage, torque, etc.), and diagnostic information.
Rotary Encoder — Used to access the Q9 ASD menu selections, change the value of a displayed
parameter, and performs the Enter key function. Turn the Rotary Encoder either clockwise or
counterclockwise to perform the Up or Down functions of the displayed menu selection. Press the Rotary
Encoder to perform the Enter (select) function.
Local/Remote Key — Toggles the system to and from the Local and Remote modes. The LED is on
when the system is in the Local Command mode. The Local mode allows the Command and Frequency
control functions to be carried out via the EOI.
The Remote mode enables the Command and Frequency control functions to be carried out via the
Terminal Board, RS485, Communication Card, or Pulse Input. The selection may be made via
Program
Utility Group Command Mode and Frequency Mode 1, respectively.
ESC Key — Returns the system to the previously viewed menu item. Subsequent Escape key activation
scrolls through the Root Menu until reaching the Frequency Command screen (See Figure 25 on pg.
37). Further ESC key entries are ignored.
Run Key — Issues the Run command while in the Local mode. The Run key LED Illuminates green
while stopped. Illuminates red while running or while exciting the motor.
Mode Key — Provides a means to access the five root menus. Pressing the Mode Key key repeatedly
loops the system through the five root menus (See Figure 25 on pg. 37). While looping through the root
menus, the Program menu will display the default Program root menu screen item or the Program sub-
menu item being accessed prior to pressing the Mode key.
Stop-Reset Key — This key has three functions.
1. Issues the Off command (decelerates to Stop at the programmed rate; F721) if pressed once while
in the Local mode.
2. Initiates an Emergency Off Fault if pressed twice quickly from the Local or Remote modes. The
Emergency Off function terminates the Q9 ASD output and will apply the stopping method
selected at F603.
3. Resets active Faults and/or active Alarms if pressed twice quickly. The source of the Fault or
Alarm must be determined and corrected before normal ASD operation can resume.
Rotary Encoder
Local/Remote
Mode
Key
Escape Key
Stop-Reset Key
Key (LED)
Run Key
(LED)
Terminal...
Direct Access...
...
Protection...
Fundamental...
LCD Screen