60 Q9 ASD Installation and Operation Manual
Command Mode
Program Utility Group
The Command Mode Selection establishes the source of the command input for
the ASD. Command inputs include Run, Stop, Forward, etc. The Override
feature may supersede the Command Mode Selection setting (see Command
Mode and Frequency Mode Control on pg. 32).
Settings:
0 — Terminal Block
1 — Panel Keypad
2 — RS485 (2-Wire)
3 — RS485 (4-Wire)
4 — Communication Option Board
Direct Access Number — F003
Parameter Type — Selection List
Factory Default — Terminal Block
Changeable During Run — No
Frequency Mode 1
Program Utility Group
The Frequency Mode 1 setting establishes the source of the frequency-control
input for the ASD. The Frequency Mode 2 setting or the Override feature may
supersede the Frequency Mode 1 setting (see Command Mode and Frequency
Mode Control on pg. 32 and F200 for more information on this feature).
Settings:
1 — V/I
2 — RR
3 — RX
4 — Panel Keypad
5 — RS485 (2-Wire)
6 — RS485 (4-Wire)
7 — Communication Option Board
8 — RX2 (AI1)
9 — Option V/I
10 — UP/DOWN Frequency (Terminal Board)
11 — Pulse Input (Option)
12 — Pulse Input (Motor CPU)
Direct Access Number — F004
Parameter Type — Selection List
Factory Default — RR
Changeable During Run — No
quen
de
F003 F004