Q9 ASD Installation and Operation Manual 213
Cable/Terminal Specifications
Installation should conform to the 2008 National Electrical Code Article 110 (NEC) (Requirements for Electrical
Installations), all regulations of the Occupational Safety and Health Administration, and any other
applicable national, regional, or industry codes and standards.
Note: The following ratings are guidelines and shall not be the sole determining factor of the
lug or wire size used with the Q9 ASD. Application-specific applicables, wire insulation
type, conductor material, and local and regional regulations are but a few of the
considerations when selecting the actual lug and wire type to be used with the Q9 ASD.
Note: Cable/Terminal specifications are based on the rated current of the Q9 ASD and Do
Not include the 10% Service Factor.
Note: Use only 75° C copper wire/cable for motor and power connections.
Table 17. 230-Volt Q9 ASD Cable/Terminal/Torque Specifications.
Model
Number
VT130Q9U
Wire/Cable Size Lug Size Range
Terminal
Board Wire
Size
Torque
AWG or kcmil
Input/Output Power
Wire-Size/Lug-Capacity for
Input/Output Power
In-Lbs./N·m
Recommended Maximum 3Ø-Input 3Ø-Output
TB1 – 4
Terminals
3Ø-Input 3Ø-Output
2010 14 10
14 to 10
20
(3-core shield)
Torque to 5.3/0.6
12.4/1.4
2015 14 10
2025 14 10
2035 14 10
2055 10 10
2080 8 8 12 to 8
26.6/3
2110 8 8 10 to 4
2160 63
8 to 2 47.8/5.4
2220 43
2270 33
4 to 1/0 212/24
2330 22
2400 1/0 4/0
2 to 300 360/412500 2/0 4/0
2600 4/0 4/0