INSTALLATION DIAGRAM OF INDOOR AND OUTDOOR UNITS
Part
code
Parts name Q’ty
A
Refrigerant piping
Liquid side  :  Ø6.35 mm
Gas side  :  Ø9.52 mm
    (RAS-10, 13N3KV(R) Series)
 : Ø12.70 mm
 (RAS-16N3KV(R) Series)
One
each
B
Pipe insulating material
(polyethylene foam, 6 mm thick)
1
C
Putty, PVC tapes
One
each
Optional Installation Parts
•  Secure the outdoor unit with fi xing bolts and nuts if the unit is likely to be 
exposed to a strong wind.
•  Use Ø8 mm or Ø10 mm anchor bolts and nuts.
•  If it is necessary to drain the defrost water, attach drain nipple 9 and cap 
water proof ! to the bottom plate of the outdoor unit before installing it.
Fixing bolt arrangement of outdoor unit
 
Insulate the refrigerant pipes separately 
with insulation, not together.
2
3
8
6
4
Insert the cushion between the indoor 
unit and wall, and tilt the indoor unit for 
better operation.
For the rear left and left piping
Wall
Make sure to run the drain hose sloped 
downward.
Do not allow the drain hose to get slack.
Cut the piping 
hole sloped 
slightly.
The auxiliary piping can be connected to 
the left, rear left, rear right, right, bottom 
right or bottom left.
Right
Rear 
right
Bottom
right
Rear
left
Bottom left
Left
6 mm thick heat resisting
polyethylene foam
1
Batteries
Flat head
wood screw
Remote control holder
Vinyl tape
Apply after carrying
out a drainage test.
Wireless remote control
Saddle
Extension
drain hose
(Not available,
provided by installer)
Shield pipe
Filter
(Attach to the front panel.)
Air fi lter
Hook
Installation
plate
Hook
65 mm or more
170 mm or more
170 mm or more
600 mm or more
100 mm or more
100 mm or more
600 mm or more
600 mm or more
Remark :
•  Detail of accessory and installation parts can see in the accessory 
sheet.
•  Some pictures might be different from the actual parts.
6 FILTER
N3KVR
5
Filter
8
Flat head
wood screw
&
(
Flat head
wood screw
Battery cover
The provided Remote Controller is a wireless type, 
which also can be used as a wire.
Please see “How to Connect The Remote Controller 
for Wired Operation”, in case of wired control is 
required.
Drain outlet
Air inlet
Air outlet
125 mm
108 mm
Ø25 mm
28 mm
320 mm
86 mm
102 mm
600 mm
90 mm
Book 1110251262-1.indb   2Book 1110251262-1.indb   2 7/13/12   8:59 AM7/13/12   8:59 AM