2-2. Operation Characteristic Curve
– 5 –
2-3. Capacity Variation Ratio According to Temperature
<Cooling>
50
55
60
65
70
75
80
85
90
95
100
105
32 33 34 35 36 37 38 39 40 41 42 43 44 45 46
Outdoor temp. (℃)
Capacity ratio (%)
Conditions
Indoor:DB27℃/WB19℃
Indoor air flow:High
Pipe length:5m
<Heating>
0
20
40
60
80
100
120
-15 -10 -5 0 5 10
Outdoor temp. (℃)
Heating Capacity ratio (%)
Condition
Indoor:DB20℃
Indoor air flow:High
Pipe length:5m
Capacity ratio 100% is 3.2kW
Capacity ratio 100% is 2.5kW
FILE NO. SVM-10029
<Cooling>
0
1
2
3
4
5
6
7
8
9
10
0 102030405060708090100110120
Compressor speed (rps)
Current (A)
<Heating>
0
1
2
3
4
5
6
7
8
9
10
0 102030405060708090100110120
Compressor speed (rps)
Current (A)