19
6-2. Operation Data
<Cooling>
<Heating>
NOTES :
(1) Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
(2) Connecting piping condition : 5 m
Temperature
condition (°C)
Indoor Outdoor
27/19 35/
Heat exchanger
pipe temp.
T1 (°C) T2 (°C)
9 to 11 49 to 50
Model
name
13UKV-E
Standard
pressure
P (MPa)
0.8 to 1.0
Indoor fan
mode
High
Outdoor fan
mode
High
Compressor
revolution
(rps)
77
Temperature
condition (°C)
Indoor Outdoor
20/ 7/6
Heat exchanger
pipe temp.
T1 (°C) T2 (°C)
42 to 44 0 to 3
Model
name
13UKV-E
Standard
pressure
P (MPa)
2.5 to 2.7
Indoor fan
mode
High
Outdoor fan
mode
High
Compressor
revolution
(rps)
83