27
0
0.5
1
1.5
2
5.0
5.5
(Room temp.)
(Set temp.)
Set
temp.
[FAN AUTO]
*
2
*
1
LOW
M+
HIGH
8-2-2. DRY Operation
(The Remote Controller MODE Button
is Set to the DRY
Position)
Once the setting is made, the operation mode is
memorized in the microcomputer so that the same
operation can be effected thereafter simply by
pushing [START/STOP] button.
Dry operation signal is transmitted to outdoor unit.
The Cooling operation giving priority to dehumidi-
fying, which restrains the indoor fan speed and
compressor motor speed, is performed.
The indoor fan motor operates as shown in Fig. 8-
2-5. (Fan speed is AUTO only.)
The outdoor fan motor operates as described in
Table 8-1-3, and the compressor motor speed
according to the operation command signal sent
from the indoor unit.
NOTE :
*1 : Middle motor speed between L and SUL
Fig. 8-2-5 Setting of air flow
8-2-3. Heating Operation
Transferring of heating operation signal from indoor
unit to outdoor unit starts.
The indoor fan motor operates by the room tempera-
ture when selecting AUTO of FAN as shown in
Fig. 8-2-6, and operates with a set air flow when
selecting Low to High .
However, to prevent cold draft, revolution speed of
the fan is restricted by indoor heat exchanger when
air flow is AUTO (Fig. 8-2-7) and starting of FAN
Manual.
[Basic control]
*1, *2 : Approximate revolution speed of M+ and L to
linear according to temperature.
Fig. 8-2-6 Setting of air flow
[Cold draft preventing control]
The upper limit of fan revolution speed is shown
below.
Fig. 8-2-7 Cold draft preventing control
NOTES :
(1) Stops for 2 minutes after thermostat-OFF.
(2) 24°C when the set temp. is 24°C or more
Set temp. when the set temp. is below 24°C
(3) SUL : Super ultra low
0.5
0
+0.5
+1.0
+1.5
+2.0
+2.5
*1
L
SUL
(Room temp.) (Set temp.)
Set
temp.
[In starting and in stability]
FAN AUTO
FAN Manual
In starting
Until 12 minutes passed after operation start
When 12 to 25 minutes passed after
operation start and room temp. is 3°C or
lower than set temp.
Room temp. < Set temp. 4°C
In stability
When 12 to 25 minutes passed after operation start
and room temp. is higher than (set temp. 3°C)
When 25 minutes or more passed after operation
start
Room temp. Set temp. 3.5°C
33
*
3
*
2
32
44
43
20
19
31
30
A
A 8
A + 4
A 8
HIGH
SUL
SUL
FAN
AUTO
Starting
of FAN
Manual
Approximate
revolution speed
of HIGH and SUL
linear by Tc.
Stop
( NOTE :
*
1)