– 27 –
Item
2. Indoor fan
motor control
Operation flow and applicable data, etc.
<In cooling operation>
(This operation controls the fan speed at indoor unit side.)
The indoor fan (cross flow fan) is operated by the phase-
control induction motor. The fan rotates in 5 stages in
MANUAL mode, and in 5 stages in AUTO mode, respec-
tively. (Table 1)
Description
* Symbols
UH : Ultra High
H : High
M+ : Medium+
M : Medium
L+ : Low+
L: Low
L- : Low–
UL : Ultra Low
SUL : Super Ultra Low
* The fan speed broadly varies due
to position of the louver, etc.
The described value indicates one
under condition of inclining
downward blowing.
1) When setting the fan speed to L,
L+, M, M+ or H on the remote
controller, the operation is
performed with the constant
speed shown in Fig. 1.
2) When setting the fan speed to
AUTO on the remote controller,
revolution of the fan motor is
controlled to the fan speed level
shown in Fig. 2 and Table 1
according to the setup tempera-
ture, room temperature, and heat
exchanger temperature.
(Fig. 1)
(Fig. 2)
(Table 1) Indoor fan air flow rate
+2.5
Ta
[
˚C
]
+2.0
+1.5
+1.0
+0.5
Tsc
a
b
c
d
e
M+(WB)
*3
*4
*5
L(W6)
Air volume AUTO
L
L+
M
M+
H
W6
(L + M) / 2
W9
(M + H) / 2
WC
Indication
Fan speed
Fan speed setup
COOL ON
AUTO
MANUAL
*3 : Fan speed = (M + –L) x 3/4 + L
*4 : Fan speed = (M + –L) x 2/4 + L
*5 : Fan speed = (M + –L) x 1/4 + L
(Linear approximation
from M+ and L)
FILE NO. SVM-11029
Fan speed
level COOL HEAT DR
Y
Fan speed Air flow rate
(rpm) (m3/h)
WF UH 1510 735
WE H 1510 735
WD UH M+ 1480 717
WC H 1430 686
WB M+ 1280 594
WA
W9 M L+ 1150 514
W8 L 1000 421
W7 L+ L- L+ 980 409
W6 L L 920 372
W5 L- UL L- 900 360
W4 UL UL 840 323
W3 SUL SUL 770 280
W2 SUL 620 187
W1 520 126
RAS-16SKV2-E1
UH
H
M
M+
M
1220 557