EasyManua.ls Logo

Toshiba RAS-18UAX2 - Ras-18 Ukp-Ar2; Ras-18 Ua-Ar2

Toshiba RAS-18UAX2
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
29
FILE NO. SVM-03010(1)
5-7. RAS-18UKP-AR2 / RAS-18UA-AR2
Indoor unit
Cross flow fan
Compressor
Condenser
Propeller fan
Outdoor unit
PH250X3-4LM
O.D.:12.7 mm O.D.:6.35 mm
Packed valve
(12.7)
Packed valve
(6.35)
T
P
Refrigerant
R22 1.17 kg
Evaporator
0.39 m
(Connecting pipe)
12.7
0.49 m
(Connecting pipe)
6.35
Mark ( ) means check points of Gas Leak
Capillary tube
2.0x1000 s
Capillary tube
0.8x900 s
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
Standard 0.4 10.0 High 27/19 35/24
Cooling High temperature 0.6 13.0 High 32/23 52/31
Low temperature 0.3 2.0 Low 21/15 21/15
Fan speed
(indoor)
50 Hz
Standard
pressure
P
(MPaG)
Surface temp. of heat
exchanger interchanging
pipe
T
(°C)

Table of Contents

Related product manuals