FILE NO. SVM-04032
25
5-4. RAS-18UFPX3-T2 / RAS-18UAX3-T2
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
Standard 0.4 10.0 High 27/19 35/24
Cooling High temperature 0.6 12.0 High 32/23 43/26
Low temperature 0.3 2.0 Low 21/15 21/15
50Hz
Fan speed
(indoor)
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
Standard
pressure P
(MPaG)
Surface temp. of heat
exchanger interchanging
pipe T (°C)
Indoor unit
Multi blade fan
Condenser
Propeller fan
Outdoor unit
O.D.:6.35 mm
Packed valve
(15.88)
Packed valve
T
Refrigerant
R-22 1.47 kg
Evaporator
Capillary tube
2.0x800
S
0.49m
(Connecting pipe)
6.35 mm
(∅6.35)
Mark ( ) means check points of Gas Leak
P
O.D.:15.88 mm
0.39m
(Connecting pipe)
15.88 mm
15.88 mm
0.39m
(Flexible pipe)
Accumulator
Compressor
PH210T2-4L7