EasyManua.ls Logo

Toshiba RAS-18UAX3 - 9-6. Troubleshooting for Indoor Unit

Toshiba RAS-18UAX3
93 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FILE NO. SVM-04032
62
[0C Indoor TA sensor error]
[0d Indoor TC sensor error]
[18 outdoor TE sensor error]
Is CN03 (TA sensor connector)
connected properly?
YES
NO
YES
NO
Is TA sensor resistance value
(10 k at 25°C) normal?
Indoor P.C. board is defective.
Replace TA sensor.
Replace P.C. board.
Connect CN03
properly.
Is TE sensor connector
connected properly?
Is TE sensor resistance value
(10 k at 25°C) normal?
Is CN01 (TC sensor connector)
connected properly?
YES
NO
YES
NO
Is TC sensor resistance value
(10 k at 25°C) normal?
Indoor P.C. board is defective.
Replace TC sensor.
Replace P.C. board.
Connect CN01
properly.
YES
NO
YES
NO
Indoor P.C. board is defective.
Replace TE sensor.
Replace P.C. board.
Connect connector
properly.

Table of Contents

Related product manuals