26
FILE NO. SVM-03010(1)
Surface temp. of heat
exchanger interchanging
pipe
T
(°C)
5-4.RAS-24UKPX-1 / RAS-24UAX-1
RAS-24UKPX-T-1 / RAS-24UAX-T-1
Evaporator
Indoor unit
Cross flow fan
Cooling
Cooling
Compressor
Condenser
Propeller fan
Outdoor unit
2JS386DJSM464
Cooling
O.D.:15.88 mm O.D.:6.35 mm
Cooling
Gas container connection (Reinstall etc.)
Packed valve
(
6.35)
Packed valve
(
15.88)
0.39 m
(Connecting pipe)
15.88
0.49 m
(Connecting pipe)
6.35
T
P
Refrigerant
R22 1.63 kg
Mark ( ) means check points of Gas Leak
Capillary tube
2.0 x650 s
* SASO Standards condition
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
Standard 0.4 11.0 High 27/19 35/24
Cooling High temperature 0.7 12.0 High 32/23 52/31*
Low temperature 0.3 1.0 Low 21/15 21/15
Fan speed
(indoor)
50 Hz
Standard
pressure
P
(MPaG)