7-2. Operation Data
<Coolin
>
Tempeature Model name Standard Heat exchanger Indoor Outdoor Compressor
condition(°C) RAS- pressure pipe temp. fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
27/19 35/- 18SKV-E 0.9 to 1.1 11 to 13 40 to 42 High High 67
18SKVR-E 0.9 to 1.1 11 to 13 40 to 42 High High 67
22SKV-E 0.9 to 1.1 11 to 13 41 to 43 High High 77
22SKVR-E 0.9 to 1.1 11 to 13 41 to 43 High High 77
<Heating>
Tempeature Model name Standard Heat exchanger Indoor Outdoor Compressor
condition(°C) RAS- pressure pipe temp. fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
20/- 7/6 18SKV-E 2.5 to 2.6 40 to 42 1 to 3 High High 79
18SKVR-E 2.5 to 2.6 40 to 42 1 to 3 High High 79
22SKV-E 2.6 to 2.8 42 to 44 0 to 2 High High 84
22SKVR-E 2.6 to 2.8 42 to 44 0 to 2 High High 84
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchaner path U bent.
(Thermistor themometer)
2. Connecting piping condition 7.5 m
– 22 −