– 25 –
FILE NO. SVM-03010(1)
5-3. RAS-24UKP-E-1 / RAS-24UA-E-1
RAS-24UKP-AR-1 / RAS-24UA-AR-1
* SASO Standard’s condition
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
Standard 0.4 11.0 High 27/19 35/24
Cooling High temperature 0.7 12.0 High 32/23 52/31*
Low temperature 0.3 1.0 Low 21/15 21/15
Fan speed
(indoor)
50 Hz
Standard
pressure 
P
(MPaG)
Evaporator
Indoor unit
Cross flow fan
Cooling
Cooling
Compressor
Condenser
Propeller fan
Outdoor unit
PH280X3-4MS
Accumulator
Cooling
O.D.:15.88 mm O.D.:6.35 mm
Cooling
Gas container connection (Reinstall etc.)
Packed valve
(∅6.35)
Packed valve
(∅15.88)
0.39 m
(Connecting pipe)
∅15.88
0.49 m
(Connecting pipe)
∅6.35
T
P  
Refrigerant
R22 1.63 kg
Mark (        ) means check points of Gas Leak
Capillary tube
∅0.8x400 s
Capillary tube
∅2.4x1400 s
Surface temp. of heat
exchanger interchanging
pipe 
T
 (°C)