FILE NO. SVM-02008
– 16 –
4-6. Outdoor Unit (RAS-24UAH-E)
No. Parts name Type Specifications
Output (Rated) 2200W, 2poles, 1 phase, 220 – 240V, 50Hz
1 Compressor PH310X3-4MM Winding resistance () Red-Black White-Black
(at 20°C) 0.8 2.16
Output (Rated) 51W, 6poles, 1phase, 220 – 240V, 50Hz
2 Fan motor (for outdoor) KPG6-71SB5P-T1 Winding resistance () Red-Black White-Black
(at 20°C) 64.4 127.4
3
Running capacitor
SK45FMP3.5U2 AC 450V, 3.5µF
(for fan motor)
4
Running capacitor
SK42CMP60U1 AC 420V, 60µF
(for compressor)
5 Solenoid coil
VHV AC 220 – 240V
(for 4-way valve)
6 Thermo sensor TE / TD 10k at 25°C / 50k at 25°C
7 Magnetic relay CLK-35J 220 – 240V, 50Hz
8 Transformer TT-05 220 – 240V
9 Microcomputer TMP47C840N
10 Varistor (R73, 74, 86) 15G471K 470V
11 Fuse (F01) MT3 T5A, 250V
No. Parts name Type Specifications
Output (Rated) 2200W, 2poles, 1phase, 220 – 240V, 50Hz
1 Compressor PH280X3-4MS Winding resistance () Red-Black White-Black
(at 20°C) 2.72 0.82
Output (Rated) 51W, 6poles, 1phase, 220 – 240V, 50Hz
2 Fan motor (for outdoor) MMF-230-65I Winding resistance () Red-Black White-Black
(at 20°C) 71.2 139.0
3
Running capacitor
SK45FMP3.5U2 AC 450V, 3.5µF
(for fan motor)
4
Running capacitor
SK42CMP45U1 AC 420V, 45µF
(for compressor)
5 Magnetic relay CLK-35J 220 – 240V, 50Hz