EasyManua.ls Logo

Toshiba RAS-24UAH-E - Remote Control Troubleshooting; Setting and Display Issues

Toshiba RAS-24UAH-E
83 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FILE NO. SVM-02008
23
5-6. RAS-24UFP-E / RAS-24UA-E
RAS-24UFPX / RAS-24UAX
RAS-24UFP-AR / RAS-24UA-AR
RAS-24UFPX-T / RAS-24UAX-T
* SASO Standards condition
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
Standard 0.4 11.0 High 27/19 35/24
Cooling High temperature 0.7 12.0 High 32/23 52/31*
Low temperature 0.3 1.0 Low 21/15 21/15
50Hz
Fan speed
(indoor)
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
Standard
pressure P
(MPaG)
Surface temp. of heat
exchanger interchanging
pipe T (°C)
Evaporator
Indoor unit
Multi blade fan
Cooling
Compressor
Condenser
Propeller fan
Outdoor unit
Capillary tube
2.4x1400S
Liquid tank
25x140S
PH280X3-4MS
Accumulator
Cooling
O.D.:6.35 mm
Packed valve
(15.88 )
Packed valve
(∅6.35)
0.49m
(Connecting pipe)
6.35 mm
T
P
Capillary tube
0.8x400S
Refrigerant
R-22 1.63kg
Mark ( ) means check points of Gas Leak
O.D.:15.88 mm
Cooling
0.39m
(Connecting pipe)
15.88 mm
15.88 mm
0.39m
(Flexible pipe)

Table of Contents

Other manuals for Toshiba RAS-24UAH-E

Related product manuals