Item
18. Set temp.
correction
Operation flow and applicable data, etc.
<Indoor control P.C. board (At shipment)>
Description
1. Purpose
When the difference between the
set temp. of the remote controller
and the room temp. is wide due
to the installation condition, etc,
the set temp. is corrected.
(HEAT operation only)
2. Description
The set temp. received from the
remote controller is corrected.
The correct value from –2°C to
+4°C is changed by the jumper
wire on P.C. board of the indoor
microcomputer.
J umper wire setup
J 801 J 802
××
×
¡
¡
×
¡¡
HEAT
shift value
–2
+4
+2
0
Jumper wire
J801
J802
J803
J804
<In HEAT operation>
At shipment
¡: With Jumper wire
×
: Cut Jumper wire