– 22 –
Outdoor Unit : RAS-4M27YAV-E
<Heating>
System Compressor Fan motor FLA
Voltage range Power supply
Combination of
indoor unit operation
Hz
Volts-
Ph.
Min. Max. MCA ICF
MOCP
(Amps)
MSC RLA Indoor Outdoor
10 ––– 7.88 7.88 20 5.78 5.78 0.15 x 1 = 0.15 0.5
13 ––– 11.20 11.20 20 8.44 8.44 0.15 x 1 = 0.15 0.5
1 unit
16 ––– 13.15 13.15 20 10.00 10.00 0.15 x 1 = 0.15 0.5
10 10 –– 11.45 11.45 20 8.52 8.52 0.15 x 2 = 0.30 0.5
13 10 –– 12.66 12.66 20 9.49 9.49 0.15 x 2 = 0.30 0.5
16 10 –– 13.55 13.55 20 10.20 10.20 0.15 x 2 = 0.30 0.5
13 13 –– 13.55 13.55 20 10.20 10.20 0.15 x 2 = 0.30 0.5
16 13 –– 14.78 14.78 20 11.18 11.18 0.15 x 2 = 0.30 0.5
2 units
16 16 –– 15.66 15.66 20 11.89 11.89 0.15 x 2 = 0.30 0.5
10 10 10 – 12.51 12.51 20 9.25 9.25 0.15 x 3 = 0.45 0.5
13 10 10 – 12.80 12.80 20 9.48 9.48 0.15 x 3 = 0.45 0.5
16 10 10 – 12.80 12.80 20 9.48 9.48 0.15 x 3 = 0.45 0.5
13 13 10 – 12.80 12.80 20 9.48 9.48 0.15 x 3 = 0.45 0.5
16 13 10 – 13.08 13.08 20 9.70 9.70 0.15 x 3 = 0.45 0.5
13 13 13 – 13.08 13.08 20 9.70 9.70 0.15 x 3 = 0.45 0.5
16 16 10 – 13.35 13.35 20 9.92 9.92 0.15 x 3 = 0.45 0.5
16 13 13 – 13.35 13.35 20 9.92 9.92 0.15 x 3 = 0.45 0.5
16 16 13 – 13.35 13.35 20 9.92 9.92 0.15 x 3 = 0.45 0.5
3 units
16 16 16 – 13.63 13.63 20 10.14 10.14 0.15 x 3 = 0.45 0.5
10 10 10 10 11.38 11.38 20 8.22 8.22 0.15 x 4 = 0.60 0.5
13 10 10 10 11.38 11.38 20 8.22 8.22 0.15 x 4 = 0.60 0.5
16 10 10 10 12.20 12.20 20 8.88 8.88 0.15 x 4 = 0.60 0.5
13 13 10 10 12.20 12.20 20 8.88 8.88 0.15 x 4 = 0.60 0.5
16 13 10 10 12.20 12.20 20 8.88 8.88 0.15 x 4 = 0.60 0.5
13 13 13 10 12.20 12.20 20 8.88 8.88 0.15 x 4 = 0.60 0.5
16 13 13 10 12.20 12.20 20 8.88 8.88 0.15 x 4 = 0.60 0.5
13 13 13 13 12.20 12.20 20 8.88 8.88 0.15 x 4 = 0.60 0.5
4 units
16 16 10 10
50 or 60 230–1 198 264
12.20 12.20 20 8.88 8.88 0.15 x 4 = 0.60 0.5
NOTE :
Model of Indoor unit 10 : RAS-M10UKV-E3, 13 : RAS-M13UKV-E3, 16 : RAS-M16UKV-E3
MCA : Minimum Circuit Amps.
ICF : Maximum Instantaneous Current Flow (Equivalent to MCA in case of inverter air conditioner)
MOCP: Maximum Overcurrent Protection (Fuse only)
MSC : Maximum Starting Current
FLA : Full Load Amps.
RLA : Rated Load Amps. RLA under conditions on the right.
DB WB
Indoor temp. (°C) 20 —
Outdoor temp. (°C) 7 6