15
UNIT
SET
CL
UNIT No.
CODE No.
SET DATA
R.C. No.
Operation procedure
1 2 3 4 5 6
7 8 9 10 11
End
2, 5,
8
3, 6,
9
1
4, 7, 10
11
Data Item code
Manual address setup from remote controller
In case to decide an address of the indoor unit prior to finish of indoor electric wiring work and unpracticed outdoor
electric wiring work (Manual setup from wired remote controller)
Arrange indoor unit in which address
is set up and the wired remote controller to 1 : 1.
Turn on the power.
1
Push simultaneously
SET
+
CL
+ buttons
for 4 seconds or more.
LCD changes to flashing.
2
Using the setup temp. / buttons,
set
12 to the item code.
3
Using the timer time / buttons, set up
the line address.
(Match it with the line address on the interface P.C.
board of the header unit in the identical refrigerant line.)
4
Push
SET
button.
(OK when display goes on.)
5
Using the setup temp. / buttons,
set
13 to the item code.
6
Using the timer time / buttons, set up
the indoor address.
7
Push
SET
button.
(OK when display goes on.)
8
Using the setup temp. / buttons,
set 14 to the item code.
9
Using the timer time / buttons, set
Individual =
0000 , Header unit = 0001 ,
Follower unit =
0002 .
10
Push
SET
button.
(OK when display goes on.)
11
Push button.
Setup operation finished.
(Status returns to normal stop status.)
(Line address)
(Indoor address)
(Group address)
(Cabling example in 2 lines)
In the above example, under condition of
no inter-unit wire of the wired remote
controller, set the address after individual
connecting of the wired remote controller.
Line 1
Header Follower
Indoor
Outdoor
Line address 1
Indoor address
1
Group address
1
Line 2
Remote
controller
1
2
2
1
3
2
2
1
2
2
2
2
Group address
Individual : 0000
Center unit : 0001
Terminal unit : 0002
} In case of group control
7
ADDRESS SETUP