E6581539
- 10 -
4. Parameters
4.1. Communication parameters
Set up the inverter parameters as follows. To update, reset of inverter. If these parameters are not
set to correct value, this unit can not work normally.
Title Function Description
 Network Time-Out
0: No action
Unit: 0.1 sec, Setting range: 1 - 1000
0000 *
f851
Operation at
communication error by
disconnection
0: Inverter stop, communication command,
frequency mode open (by
cmod, fmod)
1: None (continued operation)
2: Deceleration stop
3: Coast stop
4: Network error (
err8 trip)
5. Preset speed operation command
(Operating at the preset speed operation
frequency set with
f852)
0
f852
Preset speed operation
selection
0: None
1 - 15: Preset speed operation
0
f853
Communication option
station address monitor
(Read Only)
Station address (setup by switch) monitor -

Network option
reset setting
0: None
1: Reset option board and inverter
0
* f832 must be set up by a hexadecimal number.
ex.) 100.0 sec = 0x3E8
** When the parameters are changed, the power must be cycled (or set
f899 to 1) to the
VF-PS1 for the changes to take effect.
Note) When
cmod or fmod is set to “Communication option input”, VF-PS1 drives without
RSCMDMOD (Binary Output Object - 10) or FRCMDMOD (Binary Output
Object - 11) at each Objects.
4.2. f832: Network Time-Out
Set the communication loss action time to f832. The network loss action function starts
from receiving the properly frame message. The action of the network communication
loss is set by
f851.