5. The Metasys
®
N2 Local/Remote Operation
The example below shows how to configure the VF-PS1 for local/remote operation.
F terminal.................Operating command
R terminal................The
Metasys
®
N2 local/remote (Terminal in this example) switching
RR/S4 terminal .....Operation frequency command
<Wiring>
VF-PS1
F
R
CC
PP
RR/S4
Variable resistor for adjustmen
10k ohm
Metasys
®
N2 / local Switch
Operation command
SINK
SW1
SOURCE
CCA
<Parameter setting>
cmod(Command mode selection) = 0 (Terminal board)
fmod(Frequency setting mode selection 1) = 2 (RR/S4)
f112(Input terminal selection 2 (R)) = 48 (Metasys
®
N2/Local control)
<Operation>
R-CC terminal open: VF-PS1 is controlled as a slave device of The Metasys
®
N2.
R-CC terminal closed:
F-CC terminal short to RUN
F-CC terminal short to STOP
Output frequency is set up by the RR/S4 signal input.
Note) When “local / remote key” (2) is chosen as EASY key selection (f750) and EASY
key lamp of an inverter front panel lights, priority is most given to operation by a
panel. (Refer to the inverter instruction manual for details).
When operation/stop is by the control terminal and only a monitor is by N2, set
the functional number 48 (communication priority release) to the unused control
terminal and turn on or set 48 to the always active function selection (
f110, or
f127 or f128).
Note) The local mode of the panel has priority over Metasys
®
N2 local control.