E6581611
K-29
11
11.5 Default settings by setup menu
Function Title
Main regions
eu
(Europe)
asia
(Asia,
Oceania)
Note 1)
usa
(North
America)
(Japan)
Frequency
ul/
vl/
f170 /
f204 /
f213 /
f219 /
f330 /
f367 /
f814
50.0(Hz) 50.0(Hz)
60.0(Hz) 60.0(Hz)
Base
frequency
voltage 1, 2
240V class
vlv/
f171
230(V) 230(V) 230(V) 200(V)
500V class
400(V) 400(V) 460(V)
400(V)
V/F control mode selection
pt
0 0
0 2
Supply voltage correction
(output voltage limitation)
f307
2 2 2 3
Regenerative over-
excitation upper limit
f319
120 120 120 140
Motor rated speed
f417
1410(min
-1
) 1410(min
-1
) 1710(min
-1
) 1710(min
-1
)
Note1) Refer to section 3.1 about setup menu.