1.5. Compliance with Low voltage directive
Please carry out the below mentioned countermeasures for the Low Voltage Directive in case
of using VF-P7 as components of your products.
(1) Inverter should be installed in a panel. Pay attention to wiring openings, so that it should
prevent someone from touching live parts through the opening in case of maintenance.
2) No more than 1 cable should be connected to one earth terminal of the main terminal board. In
this case, other cables for ground should be grounded on the metal back plate and/or in the
cubicle (Refer to Fig. 4).
Refer the size of grounding cable to Table. 4.
(3) MCCB should be connected to the input side of the EMI filter.
             
                   Metal back plate
Fig. 4
Inverter
Make other terminal for
grounding
Grounding
terminal