E6581611 
 
F-30 
6 
6.6.3  Changing the functions of VIA and VIB terminals 
 
 f109 : Analog/logic input selection (VIA/VIB) 
 
 Function 
This parameter allows you to choose between analog signal input and contact signal input for the VIA 
and VIB terminals. 
 
 
[Parameter setting] 
Title  Function  Adjustment range  Default setting 
f109 
Analog/logic input 
selection  
(VIA/VIB) 
0: VIA - analog input 
VIB - analog input 
0 
1: VIA - analog input 
VIB - contact input  
2: - 
3: VIA - contact input (Sink) 
VIB - contact input  
4: VIA - contact input (Source) 
VIB - contact input  
Note) When using VIA terminal as contact input terminals, be sure to insert a resistor between P24 terminal 
and VIA terminal in sink logic connection, and insert a resistor between VIA terminal and CC terminal in 
source logic connection. (Recommended resistance: 4.7k-1/2W) 
When using VIB terminal as contact input terminals, set the upper side of slide switch SW2 to S4 side 
and then set f109. 